056T17D2118 – Marathon 0.50 HP Fan and Blower HVAC/R Motor, 3 phase, 1800 RPM, 575 V, 56Z Frame, ODP – G961
056T17D2118 Marathon Self Cooled Motors
Please advise CFM, static pressure, voltage, phase, and/or horsepower on specifications, drawings, or existing equipment for an accurate quote.
General Specifications
UPC: |
722856040800 |
Weight: |
18 LB |
Packaged Length: |
13.25 IN |
Packaged Width: |
7 IN |
Packaged Height: |
6.94 IN |
Nameplate Specifications
Output HP: |
0.50 Hp |
Output KW: |
0.37 kW |
Frequency: |
60 Hz |
Voltage: |
575 V |
Current: |
0.90 A |
Speed: |
1725 rpm |
Service Factor: |
1.25 |
Phase: |
3 |
Efficiency: |
70 % |
Power Factor: |
64 |
Duty: |
Continuous |
Insulation Class: |
B |
Design Code: |
B |
KVA Code: |
M |
Frame: |
56Z |
Enclosure: |
Drip Proof |
Thermal Protection: |
No |
Ambient Temperature: |
40 °C |
Drive End Bearing Size: |
6203 |
Opp Drive End Bearing Size: |
6203 |
UL: |
Recognized |
CSA: |
Y |
CE: |
Y |
IP Code: |
22 |
Technical Specifications
Electrical Type: |
Squirrel Cage Induction Run |
Starting Method: |
Across The Line |
Poles: |
4 |
Rotation: |
Reversible |
Resistance Main: |
36.7 Ohms |
Mounting: |
Resilient Base |
Motor Orientation: |
Horizontal |
Drive End Bearing: |
Ball |
Opp Drive End Bearing: |
Ball |
Frame Material: |
Rolled Steel |
Shaft Type: |
NEMA 56 |
Overall Length: |
10.47 in |
Frame Length: |
6.50 in |
Shaft Diameter: |
0.625 in |
Shaft Extension: |
1.97 in |
Assembly/Box Mounting: |
F1 ONLY |
Speed Characteristics
Curvepoint |
Current (Amps) |
Current (%) |
Torque (ft-lbs) |
(%) |
Speed (RPM) |
Rated Output (KW) |
Power Factor (%) |
Rated Output (Hp) |
Full Load |
1.10 |
100.0 |
1.52 |
100.0 |
1,725 |
|
|
0.50 |
Break-Down |
4.80 |
436.0 |
7.30 |
480.0 |
1,060 |
|
86.0 |
0.50 |
2/3 |
5.60 |
509.0 |
6.80 |
447.0 |
800 |
|
|
0.50 |
Locked-Rotor |
6.40 |
564.0 |
6.20 |
408.0 |
0 |
0.00 |
80.5 |
0.50 |
Pull-Up |
5.80 |
527.0 |
6.60 |
434.0 |
600 |
|
|
0.50 |
1/3 |
6.00 |
545.0 |
6.10 |
401.0 |
180 |
|
|
0.50 |
No Load |
0.85 |
77.0 |
0.00 |
0.0 |
1,800 |
|
|
0.50 |
Load Characteristics
% of Rated Load |
0 % |
25 % |
50 % |
75 % |
100 % |
115 % |
125 % |
135 % |
175 % |
Current (Amps) |
0.68 |
0.71 |
0.74 |
0.78 |
0.88 |
0.92 |
0.96 |
1.00 |
1.12 |
Rated Output (KW) |
0.13 |
0.21 |
0.31 |
0.41 |
0.51 |
0.60 |
0.63 |
0.68 |
0.87 |
Efficiency (%) |
0.0 |
44.5 |
60.5 |
68.5 |
70.0 |
72.5 |
74.5 |
74.5 |
75.0 |
Power Factor (%) |
18.0 |
29.5 |
42.0 |
53.0 |
64.0 |
68.0 |
69.5 |
72.0 |
80.0 |
Speed (RPM) |
1,800 |
1,783 |
1,770 |
1,755 |
1,725 |
1,720 |
1,715 |
1,710 |
1,685 |
Temp. Rise @ FL |
0.0 |
0.0 |
0.0 |
0.0 |
40.0 |
50.0 |
55.0 |
60.0 |
0.0 |
Torque (ft-lbs) |
0.00 |
0.37 |
0.74 |
1.10 |
1.52 |
1.80 |
2.00 |
2.10 |
2.70 |
Marathon Motors